Permit Number: T12CM06291
Parcel: 11302037E

Address:
1054 E EASY ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06291
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2012 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T12CM06291
1048 East Easy Street
New Single Family Residence (SFR)


TRANSMITTAL: November 29, 2012


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


This site is located in the R-2 zone (LUC Section 2.3.5.2.A.1). The Development Designator is "I" (LUC Sections 2.3.5.2.A.1 & 3.2.3.1.B) and the Perimeter Yard Indicator is AA (LUC Sections 3.2.3.1.B & 3.2.6.4).

Revise the dimension for the building heights on the plot plans. The setback heights are measured from design grand (ground level) to the highest point of each wall (LUC Sections 3.2.6.4 & 3.2.7.2.B). The dimensions provided are from finished floor.

Revise the elevations. The east and west elevation provided are the mirror image of what is on the plot plans.

See lot split (S07-142), on the plot plan.
12/04/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
12/10/2012 GERRY KOZIOL WWM REVIEW Denied 1: NEED PCRWRD/1ST FLOOR REVIEW OF INGRESS/EGRESS/UTILITY FOR PRIVATE SEWER RUNNING THRU 1048 E EASY ST

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2012 CPIERCE1 REJECT SHELF Completed