Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM06291
Parcel: 11302037E

Address:
1054 E EASY ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM

Permit Number - T12CM06291
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2012 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T12CM06291
1048 East Easy Street
New Single Family Residence (SFR)


TRANSMITTAL: October 15, 2012


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


This site is located in the R-2 zone (LUC Section 2.3.5.2.A.1). The Development Designator is "I" (LUC Sections 2.3.5.2.A.1 & 3.2.3.1.B) and the Perimeter Yard Indicator is AA (LUC Sections 3.2.3.1.B & 3.2.6.4).

Delineate, and dimension to the front property line, the location of the two-story section on the plot plan.

Revise the labeling of the elevation drawing as north, east, south and west elevations. (Notice that "front" elevation faces east and not the front.)

Revise the lot coverage calculations to include the vehicle use area. Also delineate the asphalt driveway, which is called out on the lot split (S07-142), on the plot plan.
10/25/2012 JASON GREEN ENGINEERING REVIEW Approved
10/29/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM06291 & T12CM06292
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

GENERAL NOTES:

" Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
" All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide segregated building drains for future gray water utilization, Ordinance #10579. Include both: a) two clothes washer standpipes, one with an above grade stub-out; b) separate gray water tub/shower and lavatory drain with exterior connection to the building sewer line at 3' from foundation.

PLUMBING PLANS:

1. Show TWO clothes washer standpipes. Provide one discharge opening plumbed to the building sewer line and a second discharge opening plumbed to the gray water collection system when discharge to an exterior wall is not feasible, City of Tucson Ordinance #10579.

MECHANICAL PLANS:

1. Show impact protection for appliances located in the garage, M1307.3.1.

ELECTRICAL PLANS:

1. Provide a lower level wall switch for illuminating all stairs and landings to include the upper landing, R303.6.1.
2. Tucson Electric Power requires a 2½" diameter service conduit, TEP SR-305.
3. Show or notate a disconnect means or a locking breaker for the water heater, E4001.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
10/31/2012 GERRY KOZIOL WWM REVIEW Denied 1: NEED PCRWRD/1ST FLOOR REVIEW OF INGRESS/EGRESS/UTILITY EASEMENT FOR PRIVATE SEWER RUNNING THRU 1048 E EASY ST (DKT & PG, OR SEQUENCE #?)