Permit Number: T12CM06245
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06245
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
10/05/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
10/05/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/05/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET F-2; DETAIL 3: PROVIDE INFORMATION FOR THE CONNECTION OF THE THREADED RODS TO THE STRUCTURE ABOVE. PROVIDE DETAILS ON THE PLANS.
2. SHEET F-3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE LETTERING ON THE DETAILS ON THIS SHEET.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/05/2012 ERIC NEWCOMB ADA REVIEW Passed
10/08/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved The installation of the 75 KVA Transformer does not appear to comply with 2005 NEC 450.13.(b), see 2005 NEC Handbook.
Ray T Majuta
PDSD, C of Tuc
Elect Plan Review
10/8/2012
Ray.Majuta@tucsonaz.gov
10/08/2012 CARL SCHULTZ FIRE REVIEW Approved
11/01/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
11/01/2012 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
11/01/2012 CPIERCE1 WATER REVIEW Needs Review
11/01/2012 CPIERCE1 WWM REVIEW Needs Review