Permit Number: T12CM06237
Parcel: 11003549A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06237
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify keynote 3 as shown on the waste and vent diagram - the note refers to a floor sink with an amalgam trap but it is shown at a bar sink with an island vent. Reference: Section 103.2.3, UPC 2006.
2. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
3. Clarify the location of the reduced pressure backflow preventers serving the vacuum pump and the model trimmer to verify that they conform to the access and clearance requirements of Section 603.3.4, UPC 2006.
4. Limit the water velocity to less than 8 fps for the copper piping (e.g. the maximum flow rates shown for the 1-1/4", 1-1/2", and 2" pipes exceed 8 FPS). Reference: Section A 6.1, UPC 2006; IAPMO IS 3-2000, Section 610.0.
5. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees. Reference: Section 707.5, UPC 2006.
10/09/2012 ROBERT SHERRY WATER REVIEW Approved
10/09/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/10/2012 SPOWELL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
10/10/2012 SPOWELL1 WWM REVIEW Needs Review