Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM06172
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 10/03/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/03/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/03/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/04/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/04/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 10/04/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The controlling plumbing code is either the 2006 IPC or the 2006 UPC. Based on your use of the IRC, this review has been done using the 2006 IPC. 2. Clarify the water service to the building; is the triplex served by a single water meter and a single ¾" water service pipe or are the three units separately served with individual meters. If the three units are not separately served, determine the water demand and revise the size of the water meter and the main water service line to limit the water velocity to less than 8 feet per second (assuming copper or plastic water service pipe). 3. Specify lead-free solder for the water piping. 4. Provide calculations to show that connecting the new fixtures to the existing water distribution system will not overload the existing pipes (i.e. excessive water velocities or pressure drops). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/28/2013 | CPIERCE1 | OUT TO CUSTOMER | Completed |