Permit Number: T12CM06144
Parcel: 122171180

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM06144
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 10-22-12
Activity: T12CM06144
Address: 3431 E Fairmount St
Applicant: Benjamin Design

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
1. Specify length of proposed porch (rafter span) R801.2.

PLUMBING PLAN:
2. The 1994 UPC is not a currently approved plumbing code.
3. Provide an accurate plumbing fixture unit schedule for the water supply calculation P2903.6.
4. Specify the diameter of the water meter and the length/diameter of the water supply line, P2903.7.

MECHANICAL PLAN:
5. The 1994 UMC is not a currently approved mechanical code.

OUTDOOR LIGHTING CODE:
6. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Model plans should specify a minimum lot size for the proposed exterior lighting.


If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
10/23/2012 CINDY AGUILAR REJECT SHELF Completed