Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM06063
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 04/10/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Five sets of structural calculations have beeen submitted for the overhead door. PLease provide the details on the drawings. |
| 04/13/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show how the requirements of Article 110.26 (E) (1), NEC 2011 have been addressed. [Initial comment: Verify that the installation of fan coil FC 2-2 and the condensate drain piping from fan coils FC 2-1 and FC 2-2 comply with all clearance requirements for electrical rooms. Reference: Section 106.1.1, IBC 2006.] 2. Provide ventilation calculations to show that an adequate flow rate of outside air is being introduced to the rooms adjacent to the area served by FC 1-4 and FC 2-4. Note that ASHRAE Standard 62.1-2007 includes air classifications that limit the recirculation of air between spaces having different classes (e.g. a science classroom or an art classroom has class 2 air and the air from these areas may not be transferred to a room with class 1 air). The room names and areas have changed from the previously approved plans: revise the calculations to reflect this and include all of the building areas. [Initial comment: All of the fan coils are scheduled to have outside air; clarify the source of the outside air for FC 1-1, FC 1-4, FC 2-1, and FC 2-4. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.] 3. Of the six fan coils that require duct smoke detectors, three have the smoke detectors located downstream of the outside air intake (FC 1-1, FC 1-2, and FC 1-5) and two do not have a duct smoke detector shown on the drawings (FC 2-1 and FC 2-3). Fan coil FC 1-3, is not required to have a duct smoke detector but the 1st floor mechanical plan indicates that one has been installed downstream of the outside air intake. [Initial comment: Smoke detectors shall be located upstream of any outside air connections. Reference: Section 606.2.1, IMC 2006.] |