Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T12CM06063
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2015 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | GENERAL 1. Please provide a updated site plan showing all the new stair changes and submit to David Rivera for a revised DP plan review. SHEET AB3 2. All handrails on the open side of the ramps are to have an intermediate horizontal bar 4" to the top of the bar as per 2009 ICC A117.1 SEction 405.9.2. Please revise the elevations accordingly. 3. Provide construction details for all ramps and stairs including structural calculations. SHEET S-1 4. Please provide a section at the existing balcony showing the connection of the new stair landing and the existing balcony. END OF REVIEW |
| 03/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the installation of fan coil FC 2-2 and the condensate drain piping from fan coils FC 2-1 and FC 2-2 comply with all clearance requirements for electrical rooms. Reference: Section 106.1.1, IBC 2006. 2. All of the fan coils are scheduled to have outside air; clarify the source of the outside air for FC 1-1, FC 1-4, FC 2-1, and FC 2-4. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. 3. Smoke detectors shall be located upstream of any outside air connections. Reference: Section 606.2.1, IMC 2006. |
| 03/25/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/26/2015 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 03/26/2015 | CPIERCE1 | REJECT SHELF | Completed |