Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM06039
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; When two or more units are tied together, the minimum drain size shall be 1" (Section 307.2.2, IMC 2006 as amended by the City of Tucson. [Original comment: Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.] |
| 10/08/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. [Original comment: Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 106.3.1, IFGC 2006.] 2. Comment not resolved; a 2" cleanout is not acceptable for a 3" waste line. [Original Comment:Provide cleanouts sized per Section 708.7, IPC 2006 (e.g. a 4" drain requires a 4" cleanout).] |
| 10/11/2012 | CAGUILA1 | WWM | REVIEW | Needs Review |