Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06039
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. 2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
| 09/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM06039 4329 N Oracle #101 1. Provide 2006 IECC Budget Lighting Calculation. 2. Indicate on plan where circuits A-17,19,24, will be located. 3. Provide circuit numbers for receptacles. 4.Show how exit fixtures are tied into circuits. 5. Provide circuit numbers for ex-fans. 6. How is LCP powered,show a diagram for LPC. 7. Provide a total load for the existing 400 amp service including the load for this space. Ray T Majuta Elect Plan Review PDSD, C of Tuc 9/27/2012 Ray.majuta@tucsonaz.gov |
| 09/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/27/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1. SHEET T2-VB: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SHEET. 2. SHEETS FP-1, A0.0, A0.1, A1.0, A2.0, A3.0: PROVIDE A NORTH ARROW ON THE PLANS. 3. SHEET A3.0; REFLECTED CEILING PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32". REVISE THE SECTION REFERENCES. 4. SHEET A3.0; SOFFIT DETAIL: AT THE DIAGONAL BRACE, PROVIDE THE BRACE SIZE AND END CONNECTIONS. 5. SHEET A5.1; DETAIL 8: AT THE DIAGONAL BRACE, PROVIDE THE BRACE SIZE AND END CONNECTIONS. 6. SHEET A7.0: A NOTE INDICATES "FOR REFERENCE ONLY". REMOVE THE NOTE. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/27/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 106.3.1, IFGC 2006. 2. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006. 3. Provide cleanouts sized per Section 708.7, IPC 2006 (e.g. a 4" drain requires a 4" cleanout). |
| 09/27/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 09/27/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/27/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/08/2012 | CAGUILA1 | WWM | REVIEW | Needs Review |