Permit Number: T12CM06039
Parcel: 10409002D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06039
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
09/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
09/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM06039
4329 N Oracle #101

1. Provide 2006 IECC Budget Lighting Calculation.
2. Indicate on plan where circuits A-17,19,24, will be located.
3. Provide circuit numbers for receptacles.
4.Show how exit fixtures are tied into circuits.
5. Provide circuit numbers for ex-fans.
6. How is LCP powered,show a diagram for LPC.
7. Provide a total load for the existing 400 amp service including the load for this space.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
9/27/2012
Ray.majuta@tucsonaz.gov
09/27/2012 ROBERT SHERRY WATER REVIEW Approved
09/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review 1. SHEET T2-VB: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SHEET.
2. SHEETS FP-1, A0.0, A0.1, A1.0, A2.0, A3.0: PROVIDE A NORTH ARROW ON THE PLANS.
3. SHEET A3.0; REFLECTED CEILING PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32". REVISE THE SECTION REFERENCES.
4. SHEET A3.0; SOFFIT DETAIL: AT THE DIAGONAL BRACE, PROVIDE THE BRACE SIZE AND END CONNECTIONS.
5. SHEET A5.1; DETAIL 8: AT THE DIAGONAL BRACE, PROVIDE THE BRACE SIZE AND END CONNECTIONS.
6. SHEET A7.0: A NOTE INDICATES "FOR REFERENCE ONLY". REMOVE THE NOTE.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/27/2012 LOREN MAKUS ENGINEERING REVIEW Approved
09/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a complete diagram of the natural gas distribution system showing the all of the loads, developed lengths, and the layout of the distribution piping. Reference: Section 106.3.1, IFGC 2006.
2. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006.
3. Provide cleanouts sized per Section 708.7, IPC 2006 (e.g. a 4" drain requires a 4" cleanout).
09/27/2012 KEN BROUILLETTE FIRE REVIEW Approved
09/27/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/27/2012 ERIC NEWCOMB ADA REVIEW Passed
10/08/2012 CAGUILA1 WWM REVIEW Needs Review