Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Permit Number - T12CM06034
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | Structure is approved per Jim Vgelsberg, based on the HEC-RAS information and discussion with Rob Shand, PE (JE Fuller). Based on the information submitted and the closing off of the existing driveways with vertical curbing flow across property is negligable. |
| 12/18/2012 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Date: 12-19-2012 Activity: T12CM06034 Address: 2723 E Linden #2 Applicant: Repp Design and Construction Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. INCLUSIVE HOME DESIGN: 1. a Provide a complete set of notes on the plan to meet the Inclusive Home Design Ordinance 10463. 2. Provide an accessible route (no step) from the public way extending throughout the entire first floor, 1003.2. 3. All pass-trough door openings on the accessible route shall have a net width of not less than 30 inches (2'8" door) 1003.5.2.1. PLUMBING PLAN: 4. Tucson Water Department limits 5/8" water meters to a maximum of 11 IRC fixture units or 15 gallons per minute. Specify a ¾" water meter upgrade. 5. All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide segregated building drains for future gray water utilization, Ordinance #10579. 6. All construction drawings submitted after March 1, 2009 for one- or two-family dwellings require a solar water heating system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater. ELECTRICAL PLAN: 7. On June 17, 2008, Mayor and Council unanimously voted to require all new residences to be solar ready for electric (PV). Starting July 1, 2009, all new single family homes or duplexes must include in the plans either a photovoltaic system or preparation for later installation of a PV system in order to receive a permit. 8. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2. 9. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11. 10. Provide subpanel equipment sized for the proposed load, E3502.2. If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |
| 12/27/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: GUEST HOUSE + SHOP - 13FU'S 2: NEED APPROVED COT PLUMBING PLANS SHOWING THAT THE EXISTING 5/8" WATER METER FOR THE EXISTING SFR UNIT #1 IS ADEQUATE TO HANDLE THE GUEST HOUSE UNIT #2 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2013 | CPIERCE1 | REJECT SHELF | Completed |