Permit Number: T12CM06013
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Exhaust ducts conveying hazardous gases (e.g. hydrogen-gas) shall not have fire dampers but the ducts shall extend directly to the exterior of the building (i.e. the duct shall be within a fire-rated shaft that extends from the fire partition to the exterior of the building). Reference: Sections 510.5.5, 510.5.7, and 510.6.1, IMC 2006.
12/20/2012 CPIERCE1 FIRE REVIEW Needs Review