Permit Number - T12CM06013
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/18/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Exhaust ducts conveying hazardous gases (e.g. hydrogen-gas) shall not have fire dampers but the ducts shall extend directly to the exterior of the building (i.e. the duct shall be within a fire-rated shaft that extends from the fire partition to the exterior of the building). Reference: Sections 510.5.5, 510.5.7, and 510.6.1, IMC 2006. |
| 12/20/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review |