Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM06013
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/03/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; in exhaust ducts conveying hazardous gases (e.g. hydrogen-gas) fire dampers are prohibited and the ducts shall extend directly to the exterior of the building. Clarify how the return duct in the UPS room is able to avoid the recirculation of contaminated air. Reference: Sections 510.5.5, 510.5.7, and 510.6.1, IMC 2006. [Original comment: Provide a design for the exhaust for the batteries in the UPS room per Section 502.4, IMC 2006.]
12/05/2012 KEN BROUILLETTE FIRE REVIEW Denied Need the quantities of batteries in gallons and type of batteries.
SEPERATE PERMITS REQUIRED FOR FIRE ALARM, FIRE SPRINKLER AND ANY OTHER SUPPRESSION SYSTEM. THESE PLANS WERE NOT REVIEWED FOR COMPLIANCE FOR THESE TYPES OF SYSTEMS.
FSD SHALL BE CONNECTED TO FIRE ALARM SYSTEM, I DID NOT SEE ANY DUCT DETECTORS. THE ACCESS CONTROL DEVICES FOR THE EGRESS DOORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM ALSO. A REMOTE ANNUNCIATOR SHALL BE PROVIDED IN THE TFD SUPERVISOR'S AREA. ONLY STROBES WILL BE NECESSARY FOR NOTIFICATION DEVICES IN THE DISPATCH AREA.
12/07/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/18/2012 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/18/2012 CPIERCE1 REJECT SHELF Completed