Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM06013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/03/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/03/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; in exhaust ducts conveying hazardous gases (e.g. hydrogen-gas) fire dampers are prohibited and the ducts shall extend directly to the exterior of the building. Clarify how the return duct in the UPS room is able to avoid the recirculation of contaminated air. Reference: Sections 510.5.5, 510.5.7, and 510.6.1, IMC 2006. [Original comment: Provide a design for the exhaust for the batteries in the UPS room per Section 502.4, IMC 2006.] |
12/05/2012 | KEN BROUILLETTE | FIRE | REVIEW | Denied | Need the quantities of batteries in gallons and type of batteries. SEPERATE PERMITS REQUIRED FOR FIRE ALARM, FIRE SPRINKLER AND ANY OTHER SUPPRESSION SYSTEM. THESE PLANS WERE NOT REVIEWED FOR COMPLIANCE FOR THESE TYPES OF SYSTEMS. FSD SHALL BE CONNECTED TO FIRE ALARM SYSTEM, I DID NOT SEE ANY DUCT DETECTORS. THE ACCESS CONTROL DEVICES FOR THE EGRESS DOORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM ALSO. A REMOTE ANNUNCIATOR SHALL BE PROVIDED IN THE TFD SUPERVISOR'S AREA. ONLY STROBES WILL BE NECESSARY FOR NOTIFICATION DEVICES IN THE DISPATCH AREA. |
12/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/18/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
12/18/2012 | CPIERCE1 | REJECT SHELF | Completed |