Permit Number: T12CM06013
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM06013
4004 S Park
TI Offices

1. Please provide information regarding Sheet E2.0, General Note 2, how this installation complies with NEC 2005 685 allowing deletion of disconnecting means for IDF Room ?
2. Sheet E5.0, the #8 grd shown on TP1 150 KVA transformer to be sized per 2005 NEC 250.66, should be
2/0 ?
3.Sheet E5.0, the supply equipment jumper from the transformer to Panel LP1 should be sized per 2005 NEC 250.102.C, sb #2 ?

Ray T Majuta
Electrical Plan Review
PDSD, C of Tuc
10/01/2012
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2012 CPIERCE1 OUT TO CUSTOMER Completed
11/19/2012 CPIERCE1 REJECT SHELF Completed