Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM06013
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/28/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM06013 4004 S Park TI Offices 1. Please provide information regarding Sheet E2.0, General Note 2, how this installation complies with NEC 2005 685 allowing deletion of disconnecting means for IDF Room ? 2. Sheet E5.0, the #8 grd shown on TP1 150 KVA transformer to be sized per 2005 NEC 250.66, should be 2/0 ? 3.Sheet E5.0, the supply equipment jumper from the transformer to Panel LP1 should be sized per 2005 NEC 250.102.C, sb #2 ? Ray T Majuta Electrical Plan Review PDSD, C of Tuc 10/01/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/19/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 11/19/2012 | CPIERCE1 | REJECT SHELF | Completed |