Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM06013
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06013
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.0; DETAIL 2: PROVIDE THE SIZE OF THE BRACING MEMBERS, THEIR SPACING, AND THE CONNECTION TO THE PARTITION WALL AND TO THE STRUCTURE ABOVE.
09/26/2012 LOREN MAKUS ENGINEERING REVIEW Approved
09/26/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/26/2012 ERIC NEWCOMB ADA REVIEW Passed
09/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
2. Provide a design for the exhaust for the batteries in the UPS room per Section 502.4, IMC 2006.
09/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/27/2012 ROBERT SHERRY WATER REVIEW Approved
09/27/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
09/27/2012 GERRY KOZIOL WWM REVIEW Passed
09/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/27/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond SEPERATE PERMITS REQUIRED FOR FIRE ALARM, FIRE SPRINKLER AND ANY OTHER SUPPRESSION SYSTEM. THESE PLANS WERE NOT REVIEWED FOR COMPLIANCE FOR THESE TYPES OF SYSTEMS.
FSD SHALL BE CONNECTED TO FIRE ALARM SYSTEM, I DID NOT SEE ANY DUCT DETECTORS. THE ACCESS CONTROL DEVICES FOR THE EGRESS DOORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM ALSO. A REMOTE ANNUNCIATOR SHALL BE PROVIDED IN THE TFD SUPERVISOR'S AREA. ONLY STROBES WILL BE NECESSARY FOR NOTIFICATION DEVICES IN THE DISPATCH AREA.