Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06013
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.0; DETAIL 2: PROVIDE THE SIZE OF THE BRACING MEMBERS, THEIR SPACING, AND THE CONNECTION TO THE PARTITION WALL AND TO THE STRUCTURE ABOVE. |
| 09/26/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/26/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/26/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. 2. Provide a design for the exhaust for the batteries in the UPS room per Section 502.4, IMC 2006. |
| 09/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/27/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/27/2012 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 09/27/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/27/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | SEPERATE PERMITS REQUIRED FOR FIRE ALARM, FIRE SPRINKLER AND ANY OTHER SUPPRESSION SYSTEM. THESE PLANS WERE NOT REVIEWED FOR COMPLIANCE FOR THESE TYPES OF SYSTEMS. FSD SHALL BE CONNECTED TO FIRE ALARM SYSTEM, I DID NOT SEE ANY DUCT DETECTORS. THE ACCESS CONTROL DEVICES FOR THE EGRESS DOORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM ALSO. A REMOTE ANNUNCIATOR SHALL BE PROVIDED IN THE TFD SUPERVISOR'S AREA. ONLY STROBES WILL BE NECESSARY FOR NOTIFICATION DEVICES IN THE DISPATCH AREA. |