Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06009
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/01/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/01/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide water pressure calculations for the rvised water distribution system. Show that the required minimum pressures for the carwash and ice making equipment are being provided. |
| 10/01/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT: SHEET 1 OF 1: PROVIDE INFORMATION ON THE BUILDING (CONSTRUCTION TYPE, OCCUPANT LOAD, OCCUPANCY TYPE, ETC.) ON THE DRAWINGS. 2. PREVIOUS COMMENT: GENERAL: PROVIDE MATERIAL SPECIFICATION NOTES ON THE DRAWINGS FOR THE BUILDING CONSTRUCTION. 3. PREVIOUS COMMENT: GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/01/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/03/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 10/03/2012 | FRODRIG2 | ZONING | REVIEW | Needs Review | |
| 10/03/2012 | FRODRIG2 | FIRE | REVIEW | Needs Review |