Permit Number: T12CM05977
Parcel: 13218171M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05977
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-1; SCOPE: THE SCOPE INDICATES "ALL WORK WILL OCCUR UNDER THE EXISTING ROOF". REVISE.
2. SHEET A-1; CODE REVIEW (EXIT WIDTH): THE NUMBER OF EXITS REQUIRED AND THE EXIT WIDTH REQUIRED ARE BASED ON 20 OCCUPANTS, WHILE THE BUILDING OCCUPANCY IS LISTED AS 24. COORDINATE.
3. SHEET A-2; FLOOR PLAN: KEYNOTE 3 REFERENCES STRUCTURAL FOR ADDITIONAL SLAB REQUIREMENTS AT THE OUTDOOR PATIO. GIVE A SPECIFIC REFERENCE.
4. SHEET A-2; FLOOR PLAN: AT THE SOUTH END, ELEVATION 2/A-3 IS INDICATED. REVISE THE REFERENCE.
5. SHEET A-2; FLOOR PLAN: ADD BUILDING ELEVATION INDICATORS1/A-3, 2/A-3, AND 3/A-3 ON THE PLAN.
6. SHEET A-2; FLOOR PLAN: CUT SECTION 8/A-3 ON THE PLAN.
7. SHEET A-3; FLOOR PLAN KEYNOTES: REVISE THE TITLE TO BUILDING ELEVATION KEYNOTES.
8. SHEET A-3; KEYNOTES: ADD KEYNOTE 4 TO THE WEST AND EAST ELEVATIONS.
9. SHEET A-3; KEYNOTES: ADD KEYNOTE 7 TO THE EAST AND SOUTH ELEVATIONS.
10. SHEET A-3; KEYNOTES: KEYNOTE 14 (EXISTING SIGN) IS NOT CORRECT ON THE WEST ELEVATION. REVISE.
11. SHEET A-3; KEYNOTES: KEYNOTE 15 WAS NOT FOUND ON THE ELEVATIONS. VERIFY.
12. SHEET A-3; SECTION 8: DETAIL 9/A-3 IS REFERENCED ON THIS SECTION. REVISE THE DETAIL INDICATOR.
13. SHEET A-4; PROJECT DATA: UNDER 'BUILDING AREA CHANGES', THE EXISTING BUILDING AREA IS LISTED AS 880 SF, WITH A PROPOSED BUILDING AREA OF 1081 SF. IN THE 'BUILDING/USE AREAS', THE BUILDING AREA IS LISTED AS 1081 SF WITH AN ADDITIONAL 541 SF AT THE PATIO (1622 SF TOTAL). CLARIFY. THE OCCUPANCY LOAD ON SHEET A-1 IS BASED ON THE 1622 SF.
14. SHEET S200; FOUNDATION PLAN: ADD A PLAN NOTE FOR THE NEW CONCRETE SLAB OVER THE EXISTING CONCRETE SLAB AT THE COVERED PATIO (SEE KEYNOTE 3 ON SHEET A-2).
15. SHEET S400; DETAILS 402, 403, AND 405: ADD A NOTE TO THESE DETAILS CONCERNING THE DEPTH OF THE FOOTING (MATCH EXISTING).
16. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/09/2012 MARTIN BROWN FIRE REVIEW Denied Multiple references to existing fire sprinkler system. I do not believe this address contains a sprinkler system. Verify, and remove all references to a sprinkler system from the plan, or indicate sprniklers will be extended to include new canopy.
10/15/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05977

1. City of Tucson Submittal Requirements: all new or relocated lighting has to be assigned a circuit and it's panel identified.
2. Panel A shows a 42KAIC ,will this be a fully rated system along with the breakers ? What is the fault current at the service ?

Ray T Majuta
Elect Pln Review,
PDSD, C of Tuc
10/16/2012
520-837/4988
10/22/2012 GERRY KOZIOL WWM REVIEW Approved THE PROPERTY OWNER ACKNOWLEDGES THAT THE EXISTING HCS CONNECTION GOES THROUGH ANOTHER PROPERTY. THE REPAIR AND MAINTENENACE OF THE HCS IS THE SOLER RESPONSIBILITY OF THE BUILDING OWNER.
10/23/2012 DAVID RIVERA ZONING REVIEW Denied From: David Rivera
Zoning review section
October 24, 2012


Zoning cannot approve the building plans until the Development Package site plan is approved.
10/24/2012 ROBERT SHERRY WATER REVIEW Approved
10/24/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/24/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/02/2012 PAUL MACHADO ENGINEERING REVIEW Approved