Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05970
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/25/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Correct the ventilation calculations per Section 403.3, IMC 2006, as amended by the City of Tucson. Use the default population values and the air distribution effectiveness (Ez) for a ceiling supply/ceiling return greater than 15 degrees Fahrenheit above the room temperature. 2. Provide balancing information for the three A/C units. |
| 09/25/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/25/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/25/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/25/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/25/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/25/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/25/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/26/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 09/26/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |