Review Details: RESUBMITTAL
Permit Number - T12CM05966
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | PREVIOUS COMMENTS WERE NOT ADDRESSED: 1. SHEET A.3; FOOTING SCHEDULE: THE FOOTING MARKED F-1 INDICATES TO SEE DETAIL 1. REVISE THE DETAIL NUMBER. 2. SHEET A.3; FOOTING SCHEDULE: THE FOOTING MARKED F-2 INDICATES TO SEE DETAIL 2. REVISE THE DETAIL NUMBER. 3. SHEET A.3; DETAILS 5, 6, AND 7: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE DETAIL NOTES. 4. SHEET A.3; DETAIL 5: THE NEW PORTION OF THE FOOTING ON THE DETAIL HAS A 1'-4" DIMENSION, WHILE THE FOOTING SCHEDULE INDICATES 3'-0" SQUARE. CLARIFY. 5. SHEET A.3; DETAIL 5: THE FOOTING DEPTH ON THE DETAIL IS INDICATED AS 1'-6", WHILE THE FOOTING SCHEDULE INDICATES 1'-8". CLARIFY. 6. SHEET A.3; DETAIL 6: THE FOOTING DEPTH ON THE DETAIL IS INDICATED AS 1'-6", WHILE THE FOOTING SCHEDULE INDICATES 1'-8". CLARIFY. 7. SHEET A.3; PARTIAL FOUNDATION PLAN 3: A DETAIL CUT THROUGH THE F-2 FOOTING ON THE RIGHT INDICATES 7/6. REVISE. 8. PREVIOUS COMMENT 4: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. THIS WAS NOT DONE ON ANY REVIEW COMMENTS. |