Permit Number: T12CM05966
Parcel: 11104151C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05966
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2012 MARTIN BROWN FIRE REVIEW Approved
09/25/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.
09/25/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/25/2012 ROBERT SHERRY WATER REVIEW Approved
09/25/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE STRUCTURAL CALCULATIONS FOR THE BUILDING ADDITION.
2. PROVIDE STRUCTURAL DETAILS AS REQUIRED.
09/25/2012 LOREN MAKUS ENGINEERING REVIEW Approved
09/25/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/25/2012 ERIC NEWCOMB ADA REVIEW Passed
09/25/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/01/2012 CHAD AMATEAU WWM REVIEW Passed
10/01/2012 CAGUILA1 ZONING REVIEW Needs Review