Permit Number: T12CM05942
Parcel: 10509550A

Address:
4821 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05942
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the type of trap primer that will be installed. The Schedule calls for a potable water supplied primer (ASSE 1018) but detail 7/P4.0 shows a trap primer connected to the tailpiece of a lavatory. Reference: Section 103.2.3, UPC 2006.
2. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006.
3. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2. Reference: Section 610.3, UPC 2006.
4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
5. Indirect waste receptors (see detail 8/P4.0) shall not be installed in locations that are not in general use by the occupants. Reference: Section 804.1, UPC 2006.
09/27/2012 ROBERT SHERRY WATER REVIEW Approved Existing 2" water meter
09/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the termination of the condensate drain for FCU-1 (see plumbing comment 5). Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 804.1, UPC 2006.
2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
10/01/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05942
4821 N Stone Av
TI Medical Offices

1. Sheet E3.0. General Note 2, "Existing branch circuit wiring may be reused if permitted by Electrical Code Enforcement Official", note to be removed ,will not be approved , must appeal to Building Official prior to obtaining permit.
2. Sheet E4.0, Provide the calculation for "Lighting Power Allawance, Lighting Power Specified"
3. Indicate on Electrical Sheets, that installation to comply with 2005 NEC 517, specify 517.13.

Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
10/02/2012
Ray.Majuta@tucsonaz.gov
10/01/2012 GERRY KOZIOL WWM REVIEW Approved