Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05942
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the type of trap primer that will be installed. The Schedule calls for a potable water supplied primer (ASSE 1018) but detail 7/P4.0 shows a trap primer connected to the tailpiece of a lavatory. Reference: Section 103.2.3, UPC 2006. 2. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 3. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2. Reference: Section 610.3, UPC 2006. 4. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks and urinals require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. 5. Indirect waste receptors (see detail 8/P4.0) shall not be installed in locations that are not in general use by the occupants. Reference: Section 804.1, UPC 2006. |
09/27/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | Existing 2" water meter |
09/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the termination of the condensate drain for FCU-1 (see plumbing comment 5). Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 804.1, UPC 2006. 2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006. |
10/01/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM05942 4821 N Stone Av TI Medical Offices 1. Sheet E3.0. General Note 2, "Existing branch circuit wiring may be reused if permitted by Electrical Code Enforcement Official", note to be removed ,will not be approved , must appeal to Building Official prior to obtaining permit. 2. Sheet E4.0, Provide the calculation for "Lighting Power Allawance, Lighting Power Specified" 3. Indicate on Electrical Sheets, that installation to comply with 2005 NEC 517, specify 517.13. Ray T Majuta Elect Plan Review PDSD, C of Tucson 10/02/2012 Ray.Majuta@tucsonaz.gov |
10/01/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |