Permit Number: T12CM05941
Parcel: 131044000

Address:
4801 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05941
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2012 STEVE SHIELDS ZONING REVIEW Approved
09/24/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
09/24/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/24/2012 ROBERT SHERRY WATER REVIEW Needs Review
09/24/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide rated partitions for all exit corridors.
a. Show all rated partitions required on the Egress Plan sheet A2.1.
b. All doors located in a rated partition must also be rated. Please schedule all rated doors as such on the door schudule.
2. Show all partitions braced to structure above, min lateral load requirements of 5 psi.
3. Provide large scale detail of the new exterior ramp and landing.
a. Show handrails and provide handrail elevation.
4. Minimum COT lettering size is 3/32" actual, upper and lower case. Revise all non-compliant lettering and resubmit.
5. A new site plan will have to be submitted for Zoning reviev because of changes in site plan:
a. Changing accessible parking spaces
b. Adding a generator
c. Adding a new landing and ramp.
d. Any other changes not noted
Please contact Steve Shields with Zoning at 837-
4956.
END OF REVIEW
09/24/2012 FRODRIG2 WWM REVIEW Needs Review
09/24/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/24/2012 LAITH ALSHAMI ENGINEERING REVIEW Approved
09/24/2012 MARTIN BROWN FIRE REVIEW Denied 1. Please provide rated partitions for all exit corridors.
a. Show all rated partitions required on the Egress Plan sheet A2.1.
b. All doors located in a rated partition must also be rated. Please schedule all rated doors as such on the door schedule.
09/24/2012 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2012 RONALD BROWN ADA REVIEW Passed