Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05931
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/25/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 09/25/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/25/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Verify with the water provider if a reduced pressure backflow prevention assembly is required for this installation. Show the size and location of the water meter. |
| 09/25/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 1 OF 2: PROVIDE INFORMATION ON THE BUILDING (CONSTRUCTION TYPE, OCCUPANT LOAD, OCCUPANCY TYPE, ETC.). 2. SHEET 2 OF 2: THE DEVELOPMENT PLAN KEYNOTES DO NOT MATCH THE PLAN. VERIFY. 3. SHEET A1.0: PROVIDE STRUCTURAL CALCULATIONS FOR THE BUILDING, INCLUDING FOOTINGS, BUILDING VERTICAL AND LATERAL ANALYSIS, AND THE CANOPY. THE CALCULATIONS PROVIDED INCLUDE VERBIAGE THAT THE FOUNDATION DESIGN IS PRELIMINARY ONLY (SEE PAGE 1). 4. GENERAL: PROVIDE MATERIAL SPECIFICATION NOTES ON THE DRAWINGS FOR THE BUILDING CONSTRUCTION. 5. GENERAL: PROVIDE PERTINENT STRUCTURAL DETAILS ON THE DRAWINGS. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/25/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/25/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a pumbing plan, including mateials, pipe sizes, valve locations, etc. |
| 09/25/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/28/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 09/28/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/28/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review |