Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T12CM05903
Parcel: 10408008C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05903
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT (12-11-12); LATERAL BRACING REQUIREMENTS AT INTERIOR PARTITIONS (DETAILS 2 AND 3 ON SHEET A1.0): THE PORTION OF THE SPECIFICATION (B2b) SHOWS A 5 PSF HORIZONTAL LOAD ON LOAD BEARING WALL FRAMING, WHICH IS BRACED AT THE TOP. THE WALLS IN QUESTION (DETAILS 2 AND 3 ON SHEET A1.0) ARE NON LOAD BEARING WALLS, AND ARE NOT BRACED AT THE TOP (THUS THE REQUIREMENT FOR BRACING). DETAIL 2/A1.0 INDICATES BRACING, BUT DOES NOT GIVE A BRACING SIZE, OR CONNECTOR SIZE AND QUANTITY AT THE TOP OF THE PARTITION WALL. A DETAIL OF THE CONNECTION OF THE BRACE TO THE EXISTING STRUCTURE ABOVE IS ALSO REQUIRED. ADD BRACING TO DETAIL 3/A1.0, OR REFERENCE 2/A1.0 AND THE NEW BRACING DETAIL TO THE STRUCTURE ABOVE.
2. GENERAL: PROVIDE A WRITTEN RESPONSE TO THIS REVIEW COMMENT.
12/21/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2013 CPIERCE1 REJECT SHELF Completed