Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM05903
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/04/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT (12-11-12); LATERAL BRACING REQUIREMENTS AT INTERIOR PARTITIONS (DETAILS 2 AND 3 ON SHEET A1.0): THE PORTION OF THE SPECIFICATION (B2b) SHOWS A 5 PSF HORIZONTAL LOAD ON LOAD BEARING WALL FRAMING, WHICH IS BRACED AT THE TOP. THE WALLS IN QUESTION (DETAILS 2 AND 3 ON SHEET A1.0) ARE NON LOAD BEARING WALLS, AND ARE NOT BRACED AT THE TOP (THUS THE REQUIREMENT FOR BRACING). DETAIL 2/A1.0 INDICATES BRACING, BUT DOES NOT GIVE A BRACING SIZE, OR CONNECTOR SIZE AND QUANTITY AT THE TOP OF THE PARTITION WALL. A DETAIL OF THE CONNECTION OF THE BRACE TO THE EXISTING STRUCTURE ABOVE IS ALSO REQUIRED. ADD BRACING TO DETAIL 3/A1.0, OR REFERENCE 2/A1.0 AND THE NEW BRACING DETAIL TO THE STRUCTURE ABOVE. 2. GENERAL: PROVIDE A WRITTEN RESPONSE TO THIS REVIEW COMMENT. |
12/21/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/11/2013 | CPIERCE1 | REJECT SHELF | Completed |