Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM05903
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT: PROVIDE ADDITIONAL INFORMATION ON DETAIL 2/A1.0 TO MEET THE REQUIREMENTS OF THE 2006 IBC SECTION 1607.13. INCLUDE THE BRACING SIZE AND SPACING, AND INDICATE THE NUMBER AND SIZE OF CONNECTORS OF THE BRACE TO THE TOP OF THE PARTITION WALL. ADD A DETAIL INDICATING THE CONNECTION OF THE BRACE TO THE EXISTING STRUCTURE ABOVE. |
| 12/11/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/11/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/17/2012 | FRODRIG2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |