Permit Number: T12CM05903
Parcel: 10408008C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05903
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT: PROVIDE ADDITIONAL INFORMATION ON DETAIL 2/A1.0 TO MEET THE REQUIREMENTS OF THE 2006 IBC SECTION 1607.13. INCLUDE THE BRACING SIZE AND SPACING, AND INDICATE THE NUMBER AND SIZE OF CONNECTORS OF THE BRACE TO THE TOP OF THE PARTITION WALL. ADD A DETAIL INDICATING THE CONNECTION OF THE BRACE TO THE EXISTING STRUCTURE ABOVE.
12/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/17/2012 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review