Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; awaiting structural review by PDSD. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of eleven 300-pound condensing units and two 1500-pound condensing units. Reference: Section 302.1, IMC 2006.
10/15/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2012 FERNE RODRIGUEZ REJECT SHELF Completed