Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM05892
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/15/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; awaiting structural review by PDSD. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of eleven 300-pound condensing units and two 1500-pound condensing units. Reference: Section 302.1, IMC 2006. |
| 10/15/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/26/2012 | FERNE RODRIGUEZ | REJECT SHELF | Completed |