Permit Number: T12CM05892
Parcel: 117132170

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05892
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05892
44 E Broadway

1. Sheet E-5, size conduits and describe conductors from Panel 2H1 to 150 KVA Transformer and from Transformer to ATS-RTB.
2. Sheet E-2, 2 panels in utility room listed as 2LD and 2L3, then there is another panel in Data Center listed as
2L3 ?
3. Show where Panel 2H1 located.
4. Show where 1600 amp MSB located, and where ATS-RTB
located.
5. Sheet E-5 indicates the 155 KVA Generator is to relocated to a weather proof enclosure ? Where and how?
6. Sheet E-5 indicated the AST-RTB is a 4 pole , how will the neutral be grounded ?
7. Sheet E-5.1, please explaine the non-coincident load in the panel schedules and why deducted ?
8. The Data Center appears to need to be in compliance with
Articcle 645. If so where would the disconnecting means be required per 645.10 ? Please note on this sheet if needs to comply with 645.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
9/27/2012
Ray.Majuta@tucsonaz.gov
09/27/2012 ROBERT SHERRY WATER REVIEW Denied Provide the size of the water meter serving this building and the total demand supplied by the water meter. Reference: Section 106.3.1, IPC 2006.
09/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of eleven 300-pound condensing units and two 1500-pound condensing units. Reference: Section 302.1, IMC 2006.
09/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/05/2012 GERRY KOZIOL WWM REVIEW Denied 1: DATA CENTER - 2ND FLOOR (38 FU'S)
2: CONNECTING TO EXISTING WATER LINE & EXISTING BUILDING SEWER PER PERMIT #PT05S07244
3: NEED TO SHOW EXISTING WATER METER SIZE, LOCATION & UPSIZING FROM WATER SUPPLIER FOR SEWER CONNECTION FEE CALCULATION

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2012 CPIERCE1 OUT TO CUSTOMER Completed
10/12/2012 CPIERCE1 REJECT SHELF Completed