Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05892
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM05892 44 E Broadway 1. Sheet E-5, size conduits and describe conductors from Panel 2H1 to 150 KVA Transformer and from Transformer to ATS-RTB. 2. Sheet E-2, 2 panels in utility room listed as 2LD and 2L3, then there is another panel in Data Center listed as 2L3 ? 3. Show where Panel 2H1 located. 4. Show where 1600 amp MSB located, and where ATS-RTB located. 5. Sheet E-5 indicates the 155 KVA Generator is to relocated to a weather proof enclosure ? Where and how? 6. Sheet E-5 indicated the AST-RTB is a 4 pole , how will the neutral be grounded ? 7. Sheet E-5.1, please explaine the non-coincident load in the panel schedules and why deducted ? 8. The Data Center appears to need to be in compliance with Articcle 645. If so where would the disconnecting means be required per 645.10 ? Please note on this sheet if needs to comply with 645. Ray T Majuta Elect Plan Review PDSD, C of Tuc 9/27/2012 Ray.Majuta@tucsonaz.gov |
| 09/27/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the water meter serving this building and the total demand supplied by the water meter. Reference: Section 106.3.1, IPC 2006. |
| 09/27/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of eleven 300-pound condensing units and two 1500-pound condensing units. Reference: Section 302.1, IMC 2006. |
| 09/27/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/05/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: DATA CENTER - 2ND FLOOR (38 FU'S) 2: CONNECTING TO EXISTING WATER LINE & EXISTING BUILDING SEWER PER PERMIT #PT05S07244 3: NEED TO SHOW EXISTING WATER METER SIZE, LOCATION & UPSIZING FROM WATER SUPPLIER FOR SEWER CONNECTION FEE CALCULATION |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/12/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 10/12/2012 | CPIERCE1 | REJECT SHELF | Completed |