Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05892
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 09/20/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/20/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/20/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/21/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/21/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 09/21/2012 | ROBERT SHERRY | WATER | REVIEW | Needs Review | |
| 09/21/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/21/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/24/2012 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 09/24/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved |