Permit Number: T12CM05876
Parcel: 125040120

Address:
2427 E 1ST ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM05876
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM05876
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:

1. The walls and soffit of the enclosed space under stairs must be protected on the enclosed side with ½" gypsum board, R311.2.2.

PLUMBING PLANS:

1. Show the water service pipe size with sufficient capacity for controlling excessive flow rates, P2903.6. A minimum 3/4" pipe is required for supplying water to the new bathroom group. A ½" pipe may serve the individual fixture.
2. Provide gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Show a ¾" gas pipe to the roof mounted gas pack.
3. Provide the BTU demand of each appliance including the new roof mounted gas pack and revise the total demand and verify the size of the supply pipe for the connected demand (may require upgrading). G2413.3 & Table G2413.4(1).

MECHANICAL PLANS:

1. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1403. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU (1 ton cooling = 12,000 BTU). The 2 ton unit requires a minimum 14" diameter return air duct.

ELECTRICAL PLANS:

1. Provide a panel schedule showing all new circuits including the Gas Pack Air Handler, E3304.11 & E3606.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
10/11/2012 CPIERCE1 WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2012 CPIERCE1 OUT TO CUSTOMER Completed