Permit Number: T12CM05769
Parcel: 11011368C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05769
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
09/17/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide specifications for the new exhaust fan (e.g. Manufacturer, Model, CFM @ what static pressure, electrical data, etc.).
2. Describe the sequence of operation for the fan.
3. Show the size of the new exhaust duct and the existing exhaust duct to which the new duct is to be attached.
09/17/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/17/2012 ROBERT SHERRY WATER REVIEW Denied Show the sizes of the existing water meter and its associated backflow preventor along with the total demand (i.e. GPM) on the water meter from all of the connected loads.
09/17/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-2: ONE OF THE TWO FITTING ROOMS MUST MEET ACCESSIBILITY PER IBC 2006 SECTION 1109.12.1. PROVIDE AN ENLARGED FLOOR PLAN AND PERTINENT ELEVATIONS FOR THE ACCESSIBLE ROOM.
09/17/2012 JASON GREEN ENGINEERING REVIEW Approved
09/17/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
2. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc) Reference: Sections 301.1.1 and 401.1, UPC 2006.
09/17/2012 KEN BROUILLETTE FIRE REVIEW Approved
09/17/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/17/2012 ERIC NEWCOMB ADA REVIEW Passed
09/19/2012 FRODRIG2 WWM REVIEW Needs Review