Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM05769
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/17/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/17/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide specifications for the new exhaust fan (e.g. Manufacturer, Model, CFM @ what static pressure, electrical data, etc.). 2. Describe the sequence of operation for the fan. 3. Show the size of the new exhaust duct and the existing exhaust duct to which the new duct is to be attached. |
| 09/17/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/17/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the sizes of the existing water meter and its associated backflow preventor along with the total demand (i.e. GPM) on the water meter from all of the connected loads. |
| 09/17/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A-2: ONE OF THE TWO FITTING ROOMS MUST MEET ACCESSIBILITY PER IBC 2006 SECTION 1109.12.1. PROVIDE AN ENLARGED FLOOR PLAN AND PERTINENT ELEVATIONS FOR THE ACCESSIBLE ROOM. |
| 09/17/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/17/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006. 2. Provide fixture descriptions for all plumbing fixtures. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc) Reference: Sections 301.1.1 and 401.1, UPC 2006. |
| 09/17/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 09/17/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/17/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/19/2012 | FRODRIG2 | WWM | REVIEW | Needs Review |