Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM05720
Parcel: 129020010

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05720
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2012 KEN BROUILLETTE FIRE REVIEW Denied Please provide seating plan for dining area and patio area. Indicate hardware on patio doors/gates. Occupant load appears to exceed 50 and panic hardware will be required.
09/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS; PROJECT INFORMATION: UNDER THE "BUILDING AREA" SECTION, THE SF IS LISTED AS 1127 SF. UNDER THE "OCCUPANT LOADS" SECTION, THE BUILDING SF ADDS UP TO 987 SF. CLARIFY.
2. SHEET GN; SPECIFICATIONS/GENERAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
3. SHEET A1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SECTION CUTS AND INTERIOR ELEVATIONS.
4. SHEET A1.1; FLOOR PLAN KEYNOTES: KEYNOTE 4 INDICATES TO "REFER TO DETAIL". PROVIDE THE SPECIFIC DETAIL REFERENCE.
5. SHEET A1.1; FLOOR PLAN KEYNOTES: KEYNOTE 5 INDICATES TO "REFER TO DETAIL". PROVIDE THE SPECIFIC DETAIL REFERENCE.
6. SHEET A1.1; FLOOR PLAN KEYNOTES: KEYNOTE 8 REFERENCES AN EXISTING DOOR. THE KEYNOTE IS INDICATED ON THE PLAN AT EXISTING WINDOWS. CLARIFY.
7. SHEET A1.1 (FLOOR PLAN); SHEET A3.0 (SECTION 03): SECTION 03 CUT ON THE FLOOR PLAN EXTENDS THROUGH THE PATIO, WHILE THE SECTION DOES NOT INDICATE THE PATIO. CLARIFY.
8. SHEET A1.4; PLAN 02: THE ELEVATION INDICATION 6/A4.0 IS NOT CORRECT. VERIFY.
9. SHEET A3.0; KEYNOTES: ADD A NOTE THAT INDICATES NOT ALL KEYNOTES LISTED ON THIS SHEET ARE SHOWN, AND TO REFERENCE SHEET A4.0 FOR CONTINUATION.
10. SHEET A4.0; ELEVATION 05: ON THE ELEVATION, A 4'-1" DIMENSION IS INDICATED. WHAT IS THIS DIMENSION?
11. SHEET A4.0; ELEVATION 07: PROVIDE THE LOCATION (FROM THE WALL AND FROM THE FLOOR) AND THE LENGTH OF THE VERTICAL GRAB BAR.
12. SHEET A4.0; ELEVATION 07: PROVIDE THE LOCATION (FROM THE FLOOR) OF THE HORIZONTAL GRAB BAR.
13. SHEET A4.0; KEYNOTES: ADD A NOTE THAT INDICATES NOT ALL KEYNOTES LISTED ON THIS SHEET ARE SHOWN, AND TO REFERENCE SHEET A3.0 FOR CONTINUATION.
14. SHEET A4.0: PROVIDE A NOTE CLARIFYING THE K NOTES ON THE ELEVATIONS.
15. SHEET A4.0; KEYNOTES: KEYNOTE 17 INDICATES A WATER HEATER PLATFORM. PROVIDE A REFERENCE TO DETAIL 05/A8.1.
16. SHEET S1.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS (SHEET 5): THE CALCULATIONS INDICATE A COLUMN TO BE HSS3X3X 1/4, WHILE THE PLAN INDICATES THE COLUMN (C1) TO BE A HSS 3.5" X 3.5" X 3/16". COORDINATE.
17. SHEET S1.0 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: THERE ARE NO CALCULATIONS FOR THE C2/CF2 COLUMN AND FOOTING INDICATED IN FOUR LOCATIONS. PROVIDE.
18. SHEET S1.1 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEETS 1 AND 5): THE CALCULATIONS INDICATE BEAM RB3 TO BE A 5 1/8" X 13 1/2" GLU-LAM, WHILE THE PLAN INDICATES A 3 1/8" X 13 1/2" GLU-LAM. COORDINATE.
19. SHEET S2.0; SECTIONS 1, 2, 3, 4, AND 5: A NOTE INDICATES "B.O. BEAM-RFR TO SECTION". WHAT SECTION PROVIDES THAT INFORMATION?
20. GENERAL: THERE WAS A FOOD MENU INCLUDED IN THE STRUCTURAL CALCULATIONS. THE CITY OF TUCSON APPRECIATES THAT LISTING, ALTHOUGH WE CANNOT APPROVE OR DENY THAT INFORMATION.
21. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/01/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the size of the waste pipe, wet vent, and cleanout for the hand sink and floor sink located next to the ice maker. The plumbing plan indicates an existing 3" waste line but the schedule implies a 2" waste line and cleanout. Reference: Section 103.2.3, UPC 2006.
2. Provide structural calculations for the mounting shelf for the water heater to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
3. Provide a watertight pan of corrosion-resistant material under the water heater with a drain to an approved location. Reference: Section 508.4, UPC 2006.
4. Appliances (e.g. espresso machines, coffee brewers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
5. Provide a vacuum relief for the storage-type water heater. Reference: Section 608.7, UPC 2006.
6. The maximum length of the horizontal section of a vent may not exceed one-third of the total allowable vent length noted in Table 7-5, UPC 2006 (see the vent for the gravity grease interceptor).
7. The prep sink requires indirect waste piping (as shown on sheet P1.0) but the plumbing kitchen schedule (P2.0) shows the prep sink with a direct connection. Reference: Section 801.2, UPC 2006.
8. Show that the indirect waste piping complies with the requirements of Section 803.0, UPC 2006 with respect to length.
10/03/2012 ROBERT SHERRY WATER REVIEW Approved
10/04/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/11/2012 GERRY KOZIOL WWM REVIEW Approved