Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM05689
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2012 GERRY KOZIOL WWM REVIEW Denied 1: SFR
2: CONNECTING TO EXISTING 4" HCS
3: NO PREVIOUS SEWER PERMITS HAVE BEEN FOUND - VACANT LAND PER MAPGUIDE - NEED CREDIT EVALUATION FOR CONNECTING TO EXISTING WATER METER WITH 1- 1/2" LINE FOR SEWER FEE CALCULATION - NEED WATER BILL SHOWING USER FEES BEING PAID ON WATER BILL - CHAD AMATEAU- 740-6547
09/27/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM05689
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007 and the 2006 UPC with amendments on 7/10/2007. For initial construction: Effective 1/1/2007 the Inclusive Home Design; starting 3/1/2009 Solar Water Preparation and 7/1/2009 Solar Photo-Voltaic Preparation are required for all new SFR and duplex plans. Show the code references on the plans. Amendments to adopted codes are at the City web-site http://www.tucsonaz.gov: Planning, Building, & Business; under the Building topic; Building Ordinances and Codes; Building Codes

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Update code references at Site Prep Note #3 and CMU Note #1.B, sheet A1.
" Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
" All SFR and Duplex plans submitted after March 1, 2009 require a solar water system, or future installation preparation City of Tucson Ordinance #10549 with one of the following provisions: ½"control conduit and two ¾" copper piping for water with rooftop termination; straight 3" capped sleeve; or an accessible attic (clear path 30" wide x 30" high) over the water heater. Show appropriate notation.
" All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". Show appropriate notation.
" All construction drawings submitted after June 1, 2010 for one- or two-family dwellings must provide segregated building drains for future gray water utilization, Ordinance #10579. Include both: a) two clothes washer standpipes, one with an above grade stub-out; b) separate gray water tub/shower and lavatory drain with exterior connection to the building sewer line at 3' from foundation.

FOUNDATION PLANS:

1. Notate the grade away from foundations with a minimum 6" fall within the first 10', R401.3.

FLOOR PLANS:

1. Show a maximum ½" floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1.

STRUCTURAL PLANS:

1. Notate a proposed location and weight of future Solar Panel loads on the roof framing plan for verifying the truss load carrying capacity used for the engineered truss design, R301.1 & M1401.

SECTIONS - DETAILS - NOTES:

1. Clarify if the Ramada is included on this project, R106.1.1. If so, remove the "under separate permit" notation from sheet A1. If not, delete from sheets A2, A3, A4 & E1.
2. Clarify Keynote #17 appearing at Bedroom #3, R106.1.1.

PLUMBING PLANS:

1. Provide a water hammer arrester for quick-closing valves at the clothes washer, UPC 609.10. P2903.5.
2. Provide pipe diameter between the shut off valve and water heater in compliance with P2903.7. A minimum 1-1/4" pipe is required for supplying water to more than 32 fixture units.
3. Show a provision for a future solar water system, City of Tucson Ordinance #10549.
4. Show TWO clothes washer standpipes. Provide one discharge opening plumbed to the building sewer line and a second discharge opening plumbed to the gray water collection system when discharge to an exterior wall is not feasible, City of Tucson Ordinance #10579.

ELECTRICAL PLANS:

1. Clarify the overtyped notation at the Service Load Calculation.
2. Smoke alarms are required outside each separate sleeping area, R313.2. Show a smoke alarm on the outside of the bedroom door area.
3. Add a double breaker space for future Photo Voltaic on the panel schedule, E3304.11 & E3606.2.
4. Show the location of a typical electrical panel on the Electrical Plan with 4 square feet of clear area for future Photo Voltaic equipment, E3501.6.2 & E3605.8.
5. Revise the electrical load calculation showing a minimum 3,800 volt-ampere or 16 Ampere 100% entry for future Photo Voltaic equipment, E3502.2.

OUTDOOR LIGHTING CODE

1. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Fixtures are only exempt from the total lumen budget if both of the full cut-off FCO style and located under overhangs, OLC 5.1.2.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/09/2012 SHANAE POWELL REJECT SHELF Completed