Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM05663
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Specify the materials to be used for the water piping and fittings. Reference: Section 604.0, UPC 2006. 2. Relocate the reduced pressure backflow preventers to conform to the access and clearance requirements of Section 603.3.4, UPC 2006. 3. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 4. Specify the materials to be used for the drainage piping and fittings. Reference: Section 701.0, UPC 2006. 5. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (sinks require cleanouts if they have any horizontal drains). Reference: Section 707.4, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/24/2012 | SHANAE POWELL | REJECT SHELF | Completed |