Permit Number: T12CM05663
Parcel: 133142210

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM05663
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2012 STEVE SHIELDS ZONING REVIEW Approved
09/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/11/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. The # 10 conductors are too small for RTU #1= 46 amps and #2 =37 amps.
2. The Fault Current Table shows the 400 amp disconnect at 49,007 isc the panel at 22,000aic how is this reducded to allow 22,000aic?
3. The 200 amp main disconnect(Ipresume at panel) is shown to be 45,902 isc panel rated 22,000aic, how is this reduced ?

Ray T Majuta
Elect Paln Review
9/12/2012
Ray.Majuta@tucsonaz.gov
09/11/2012 ROBERT SHERRY WATER REVIEW Approved
09/11/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
09/11/2012 ERIC NEWCOMB ADA REVIEW Passed
09/11/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/12/2012 MARTIN BROWN FIRE REVIEW Approved
09/13/2012 CPIERCE1 WWM REVIEW Needs Review
09/13/2012 PAUL MACHADO ENGINEERING REVIEW Approved