Permit Number: T12CM05621
Parcel: 11012005A

Address:
2585 N WYATT DR

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T12CM05621
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1.New term cabinate,feeder sizes [secondary] from utility x-former, ampacity,Plan Sheet E4.1 not consistant with Plan Sheets E0.1,E2.0,E2.1.
#2.Feeder ampacity to new 'ATS' and panel 'EM-1' undersized for 400 amp ocpd, from panel 'F' . Also from new generator to 'ATS'.
#3. Please submit a selective coordination analysis for circuit paths for compliace of NEC articles 517, 700. 708.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/27/2015 AROMERO4 APPROVAL SHELF Completed
01/27/2015 AROMERO4 OUT TO CUSTOMER Completed