| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | #1.New term cabinate,feeder sizes [secondary] from utility x-former, ampacity,Plan Sheet E4.1 not consistant with Plan Sheets E0.1,E2.0,E2.1. #2.Feeder ampacity to new 'ATS' and panel 'EM-1' undersized for 400 amp ocpd, from panel 'F' . Also from new generator to 'ATS'. #3. Please submit a selective coordination analysis for circuit paths for compliace of NEC articles 517, 700. 708. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/27/2015 | AROMERO4 | APPROVAL SHELF | Completed |
| 01/27/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |