| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2012 | MARTIN BROWN | FIRE | REVIEW | Denied | Unable to determine if panic hardware is installed where required. Please refer to 2006 IBC, section 1008.1.9. |
| 09/13/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. Please provide completed certification form for special inspectors as outlined in the structural drawings. SHEET A1 2. Children's toilets need to meet ICC A117.1 accessible standards: Section 604.10 for water closets, 602.2.2 for drinking fountains, and 606.2 exceptions 3 and 4 for lavatories. a. Please provide a large scale plan and interior elevations showing all these requirements. Please do not forget the grab bars. 3. Door 107A does not meet clearance requirements as per ICC A1127.1, Section 404.2.3.1, Figure (b). Being a required exit, it should have a panic bar and closer, please verify and add specifics to door schedule. 4. Show accessible toilet room signage elevation. 5. Insure all designated exit doors are indicated with an exit sign on the electrical drawings. END OF REVIEW |
| 09/20/2012 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Old Pueblo Gymnastics Academy - Expansion T12CM05598 Building Plan (1st Review) TRANSMITTAL DATE: September 20, 2012 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning can not approve the building plan until a development package has been approved. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 09/25/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide roof drainage calculations. Provide overflow protection for the roof. Reference: Sections 1101, 1106 and 1107, IPC 2006. |
| 09/26/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet (the town of Pima, Arizona is located in Graham County). Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006. |
| 09/26/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/27/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/28/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM05598 7670 E Wrightstown 1. Please clearify a few issues: a. Sheet E1.1 shows the 15KVA transformer being fed from Panel HA circuits 2,4,6 with 3 #10's b. Same sheet (E1.1) shows Panel HB fed from Panel HA with 3#1's w/#8 grd on a 100 amp breaker c. there is no panel schedule on plans for HB d. the light circuits are fed from Panel HA 1 and 3 same as HP-3 and 4, shouldn't they be from Panel HB ? 2. Please provide a location for Panel HA. Should drawing show the 100 amp circuit from Panel HA feeding Panel HB, then Panel HB feeding 15kva transformer and all circuits shown in the Panel marked HA on Sheet E0.1 ? Ray T Majuta PDSD, C of Tuc Elect Plan Review 9/28/2012 Ray.majuta@tucsonaz.gov |
| 10/05/2012 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Denied | Once development package is approved, Engineering can approve building plans. |