| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 4: THE FOOTING INDICATED IN DETAIL 05/A0.1 STILL DOES NOT MATCH DETAIL 107/S4.0. COORDINATE. 2. PREVIOUS COMMENT 9: THE REQUIRED DIMENSION FROM GRADE TO THE BOTTOM OF THE SIGN IS 7'-0" PER THE ARIZONA DEPARTMENT OF TRANSPORTATION. REVISE. 3. PREVIOUS COMMENT 15: THE DOWEL LENGTH AND MINIMUM EMBEDMENT INTO EACH SIDE OF THE CONCRETE SLAB IS NOT PROVIDED IN DETAIL 08/A4.0. REVISE. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 09/28/2012 | CPIERCE1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review |