Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T12CM05500
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the drawings to show the current scope of work. Do not show work that has been done previously. 2. Provide the manufacturer, model, and operating characteristics for the low-intensity infrared heaters. 3. Verify the configuration of the two heaters complies with the manufacturer's listing instructions. 4. Verify the gas pressure to the heaters - provide pressure regulation for the gas service. 5. Show the developed length of the gas pipes from the meter to the loads. |
| 09/24/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/24/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |