Review Date Reviewer's Name Type of Review Description Status Comments
09/04/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the drawings to show the current scope of work. Do not show work that has been done previously.
2. Provide the manufacturer, model, and operating characteristics for the low-intensity infrared heaters.
3. Verify the configuration of the two heaters complies with the manufacturer's listing instructions.
4. Verify the gas pressure to the heaters - provide pressure regulation for the gas service.
5. Show the developed length of the gas pipes from the meter to the loads.
09/24/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved