Permit Number: T12CM05475
Parcel: 99999999A

Address:
1000 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05475
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM5475
Site Lighting for 1000 E 22 St " Retreat"

1. Your submittal does not provide any information on how the lumen values are obtained. How was your total count of
1,135,000 lumens used arrived at ? Please provide your calculation.
2. Sheet ES-102 indicates all Luminares are Full Cut Off, the submitted material indicates that fixtures A, A1, E and F are not.

Ray T Majuta
Electrical Plan Review
PDSD, Tucson
9/27/2012