Permit Number: T12CM05475
Parcel: 99999999A

Address:
1000 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM05475
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. NO INFORMATION WAS GIVEN ON THE LIGHT POLES. PROVIDE STRUCTURAL CALCULATIONS AND DETAILS (ON THE DRAWINGS), INCLUDING A SITE PLAN LOCATING THOSE POLES.
08/31/2012 MICHAEL ST. PAUL ZONING REVIEW Approved
08/31/2012 JASON GREEN ENGINEERING REVIEW Approved
08/31/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Provide a calculation showing compliance with 2012
City of Tucson Outdoor Lighting Code, then submit for review,too large for walk-thur

Ray Majuta
Elect Pln Ck
DSD, City of Tucson
8/31/2012

Final Status

Task End Date Reviewer's Name Type of Review Description
09/24/2012 CINDY AGUILAR OUT TO CUSTOMER Approved