Permit Number: T12CM05419
Parcel: 11822041A

Address:
1350 S 8TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM05419
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM05419
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL NOTES:

" Provide the referenced inspection documents identified on the Scope of Work statement and remove "per direction of Lee Ray Hanley". This action is required for verifying the building is suitable "as-is" for further alteration. This permit needs to include any alterations performed since the last final inspection.

FLOOR PLANS:

1. Show compliance with R303.1 providing natural light into habitable rooms (8%) or identify appropriate exception.
2. Show compliance with R303.1 providing (4%) natural ventilation or identify appropriate exception.
3. Show compliance with R310 providing egress from the Loft (sleeping space).

STRUCTURAL PLANS:

1. Show ledger to wall connections consistent with Figure R606.11 (1) on Detail 1/S1. Change ledger bolt size and spacing for a prescriptive design, or provide an engineer's calculation, design and seal for an alternate design.

SECTIONS - DETAILS:

1. Include a 9 ½" maximum riser spacing on Detail A/A2, R311.5.8.1.

PLUMBING PLANS:

1. Show consistent code references used for the plumbing design, 2006 IRC. Change the 2009 reference at the Water Calculation Summary, and use current water fixture units rather than those shown at the Fixture Unit Calculations table.

ELECTRICAL PLANS:

1. Show the location of each outlet on the Electrical Plan, E3305.1. Include circuit #2 and clarify #3.
2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3602.2.
3. Show or notate a disconnect means or a locking breaker for the water heater, E4001.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2012 CINDY AGUILAR REJECT SHELF Completed