Permit Number: T12CM05412
Parcel: 122160010

Address:
3645 E PIMA ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM05412
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM05412
3645 E Pima
7KW Photovoltaic System

1. All Commercial PV Plans are required to be sealed by an Arizona EE.
2. Per 2005 NEC 690.64(B)2.," The sum of the ampere ratings of overcurrent devices in the circuits supplying power to a busbar or conductor shall not exceed the rating of the busbar or conductor." Panel 1W shows a rating of 225 amps, main of 225 amps and the PV circuit at 30 amps,
totaling 255 amps of overcurrent devices.
If the 2008 NEC is to be used, it must be stated on the plan, you show 2005 NEC to be used.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
9/24/2012